NOTES FOR TEST-RUN

Preparation for Filing Thermal media oil after Completion of Assembly Installation.

Two inlets are available for filling thermal media oil:
P4 Tube for filling oil into Expansion Tank, discharging excessive oil from Expansion Tank to lower tank, or testing Expansion Tank Liquid Level Controller.

The 3/4” Valve located under Circulation Pump for discharging residual oil in pipe when cleaning Filter, this also can be done through the Oil inlet where you fill thermal media oil initially.

All exhaust valves in P3 pipe line must be turned on fully, besides,all valves in main pipe line must be turned on fully, too.

NOTE:
A 13mm Bolt Plug is next to pivot of circulation pump, when filling thermal media oil initially it is may not be tightened up for the purpose of removing air during test-run; let thermal media oil fill into bearing as lubricant until full, them tighten up the bolt.